Concentration distribution of leaking flammable refrigerants from building air-conditioning systems

刘全义,张辉,刘奕,李志鹏
DOI: https://doi.org/10.16511/j.cnki.qhdxxb.2013.09.007
2013-01-01
Abstract:The risks of flammable refrigerants leaking from air-conditioning systems were analyzed using CFD simulations to simulate horizontal and vertical jets on the propane concentration inside the room. The explosive limit is used as the criterion to analyze the effect of mechanical ventilation on the propane concentration variations. The results show that the propane concentration can be held below the explosive limit by mechanical ventilation, reaching or exceeding the explosive limit only very near the leaking orifice. The refrigerant concentration distribution after leakage is greatly affected by the exhaust, with lower exhaust locations more effectively reducing the propane concentration inside the room for vertical exhaust flows with less effect for horizontal exhaust vents.