Detection and Identification of Cable Aging Using Power Line Communication Technology
Dong Liang,Hu Liu,Yanting Wang,Kaiwen Zhang,Zilun Wang,Meijuan Luo,Tao Zheng,Chen Chi,A. M. Tonello
DOI: https://doi.org/10.1109/tdei.2024.3417419
IF: 2.509
2024-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:Non-destructive inspection methods that use broadband reflecting signals to identify microscopic flaws and aging characteristics in power cables are often employed, however they suffer from limited detection distances and a single detection target. This study proposes a scheme for harnessing power line communication (PLC) devices to accomplish the detection and identification of multiple cable aging. A model of the propagation of a high-frequency carrier signal through a cable is first combined with mathematical models of various types of aging, such as water-tree aging, electric-tree aging, and thermal aging, to simulate the network channel state in the process of different insulation degradation of the cable. The channel frequency domain response (CFR) at the receiver can then reflect the incidence of cable aging, and the proposed approach, in conjunction with machine learning algorithms, can recognize different types and severity of aging under interference. Computer simulations and field experiments were conducted to validate the viability of the suggested approach, and the results shown that 98% correctness could be attained in on-line monitoring despite interference considerations. In theory, the range is doubled when compared to the reflected signal approach with the same bandwidth and power.