Abstract:Correlation technique is widely used to locate leaks in buried water pipes. If a leak exists, a distinct peak may be found in the cross-correlation function of two acquired acoustic signals. However, in practice, distinct peak in the cross-correlation function may be caused by a non-leak acoustic source occurring in or outside the pipe. And the peak not related to a leak will result in a false location. The autocorrelation functions of the two acquired signals are used to construct a new function. The power attenuation factors of leak and non-leak signals can be extracted from the new function using correlation analysis and approximate entropy. Thus, if the peak in the cross-correlation function of two acquired signals is related to the leak signal or the non-leak signal can be identified. The proposed method has been employed to locate leak in the presence of non-leak noises inside and outside pipes, and the leak location errors are less than 1m. The proposed method breaks through the limitation of traditional leak location technologies and instruments based on time delay estimation, which can only implement leak location operations at night or in quiet environment where certain pipe valves and slip are intentionally closed.