A numerical study of influence of human body movement on indoor air-flow and contaminants distribution

Hui Lin,Bin Zhao
2012-01-01
Abstract:In this paper, we present the numerical simulated results of the influence of moving human body on indoor air-flow and contaminants distribution. The human movement was simulated with the dynamic mesh model. Ventilation rate and ventilation mode, moving speed of human body and frequency of movement were main factors studied. Our findings show that the human walking disturbs the local air-flow field intensively. The flow-field with a ventilation rate of 10ACH can quickly return to steady state while the air-change rate reduced to 6 ACH and 3 ACH, or the system changed to the displacement ventilation mode, the period of influence was obviously extended. The increase of walking speed from 0 to 1.5m/s could effectively increase the air flow speed nearby. When the movement was taken only once the environment could return to steady state in 15-60 second after stop walking, but if the movement goes along, air velocity and contaminant field would significantly changed.
What problem does this paper attempt to address?