DC Operation Mode and Control Parameters Based on System Self-Organized Criticality Theory

屠竞哲,于洋,史济全,辛焕海
DOI: https://doi.org/10.3785/j.issn.1008-973x.2012.10.015
2012-01-01
Abstract:A dynamic cascading failure model including system complete dynamic characteristics was proposed in order to analyze the impact of DC transmission on the self-organized criticality(SOC) of AC/DC system.The model considered the probability characteristics of emergency control and protection device and DC system.A cascading failure Monte-Carlo simulation of the 2010 East China power grid actual system was performed by using the model.The system outage power-outage probability power law curve was calculated,and the impact of DC operation mode and control parameters on the system self-organized criticality was analyzed under different DC operation modes and control parameters.Results show that the occurrence of cascading failure and blackout can be effectively prevented by selecting the suitable DC operation mode and control parameters in certain conditions.
What problem does this paper attempt to address?