Abstract:For the uneven electrical distribution on screening electrode of ultra-high voltage AC bushing,hence often leading to corona and dielectric puncture,the electric field and voltage distribution of ultra-high voltage AC bushing are evaluated with 3D FEM.It is found that the field strength on the upper and lower arcs of the screening electrode gets higher,but on the intermediate region gets lower.By changing the structure parameters of screening electrode,the influences of shape of the electrode on electric field distribution are analyzed,and the optimization objective function is established accordingly.The neural network model is constructed to map the structure parameters of screening electrode on the optimal goal.As a result,the maximum electric field strength decreases by 20%,electric field distribution becomes more uniform,and the flashover voltage of busing is heightened.The structure of the optimized screening electrode is simple and easy to be produced.