Equal Transfer Processes-Based Distance Protection of Ehv Transmission Lines

Minghao Wen,Deshu Chen,Xianggen Yin
DOI: https://doi.org/10.1016/j.ijepes.2013.03.028
2013-01-01
Abstract:Based on the theory of equal transfer process of transmission lines,the transfer feature of the voltages used by the distance protection is different from that of the currents due to the transient characteristic of capacitive voltage transformers(CVT),which is an important reason of the transient overreach of protections.Therefore,a novel high-speed distance relay scheme was proposed in order to solve the above problem.In the novel scheme,the three-phase voltages and currents at the relay location and the voltage at the fault point were made to have the same transfer links.There are three major steps in the novel method,that is,re-structuring of the voltage at the fault point,virtual digital transferring and solving the R-L differential equation.The ATP simulation results show that the proposed method can effectively reduce the transient error caused by CVT.The distance measuring error is within 5% at approximately 15 ms after the fault occurrence.The proposed algorithm is superior to various adaptive protection algorithms based on CVT transient error estimation or source impedance ratio(SIR),which need at least 30 ms with the distance measuring error less than 5%.
What problem does this paper attempt to address?