Progress in Selecting Desiccant and Dehumidifier for Liquid Desiccant Cooling System

Xiu-Wei Li,Xiao-Song Zhang,Rong-Quan Cao,Shuo Quan
DOI: https://doi.org/10.1016/j.enbuild.2012.02.034
IF: 7.201
2012-01-01
Energy and Buildings
Abstract:Liquid desiccant cooling system (LDCS) is an alternative air-conditioning system with good energy-saving potential. Dehumidification performance is the key part of LDCS; while desiccant variety and dehumidifier influence the dehumidification performance. However, few works have been done about how to select cost-effective liquid desiccant and good performance dehumidifier. To improve, we proposed a new method for selecting a cost-effective mixed desiccant group: it combines the non-random two-liquid equation (NRTL equation) with the desiccant cost to get the mathematical form of the cost-effectiveness. Meanwhile, through the comparison experiments among different dehumidifiers, we have found out some helpful tips for dehumidifier design: it achieves better effect with rougher surface and adsorption absorption complex plan. These progresses increase the dehumidification performance by more than 50% and could make LDCS more competitive in the future market. (c) 2012 Elsevier B.V. All rights reserved.
What problem does this paper attempt to address?