Identification and Validation for Synchronous Generator Parameters Based on Recorded On-Line Disturbance Data

Shuangxi WU,Boming ZHANG,Wenchuan WU,Hongbin SUN
2012-01-01
Abstract:To improve the validity of parameters, a parameter identification and validation method is proposed for synchronous generator using recorded disturbance data. Compared with traditional off-line testing, this process can be done while the units are on-line. Robustness can't be guaranteed when all parameters are identified together. Therefore, a step-by-step identification algorithm for synchronous generator is proposed. Firstly, steady parameters are calculated from steady measurements directly. Then transient and subtransient parameters are estimated from disturbance data. What's more, transient parameters can be divided into two groups, named d-axis group and q-axis group, and each group of parameters can be estimated separately due to the decoupling characteristics of d-q axis when power angle measurement is available. At most four parameters are estimated at each step and therefore robustness of identification results can be improved. Identification results may be polluted for some reasons, such as identifiability of parameters or bad data exists in measurements. A parameter validation strategy for synchronous generator is proposed based on external sequence controlled source, which can validate parameters sensitively. The paper presents the successful applications of this technique to actual fault scenarios. Test results of the case studies demonstrate the validity of the proposed method.
What problem does this paper attempt to address?