A maximum available power algorithm for multi-infeed HVDC system based on equivalent impedance
Sicheng Wang,Shan Gao,Xin Zhao,Yu Liu,Tiancheng Song,Sufan Jiang,Dong Yu
DOI: https://doi.org/10.1016/j.ijepes.2021.106829
2021-07-01
Abstract:<p>High-voltage direct current transmission is widely used due to its asynchronous interconnection, fast and controllable transmission power adjustment and economy. The maximum available power calculation of an HVDC system is important in voltage stability analysis and control strategy design. The maximum available power is generally acquired based on repetitive power flow calculations for the system model and results in a low computational efficiency. In this paper, the equivalent impedance model of an HVDC system is deduced based on the external characteristic equivalence, and the model of an AC/DC system is converted to an AC system. For a single-infeed HVDC system, the boundary condition of the maximum available power is deduced based on the proposed impedance model. For a multi-infeed HVDC system, an equivalent model is acquired based on the impedance model, and the maximum available power algorithm is proposed. Finally, the effects of the network parameters and the operation status of neighboring HVDC links on the equivalent impedance are analyzed. The proposed method simplifies the mathematical model; hence, the computational efficiency is enhanced. The case study results demonstrate the effectiveness of the proposed method.</p>
engineering, electrical & electronic