Numerical Simulation for Impact of Excess Air Ratio on Tangential Combustion

CAI Tao,DUAN Yao-hui,QIAO Xiao-lei,JIN Yan
2013-01-01
Abstract:FLUENT software has been employed to investigate combustion characteristics in the tangentially fired furnace of a 600 MW pulverized coal boiler at different excess air ratios of 1.1,1.2 and 1.3.The results show that with the increasing of excess air ratio,air velocity and temperature in primary combustion zone increased;and CO concentration decreased due to the increasing of O2 concentration.Furthermore,the numerical simulation for impact of excess air ratio on average velocity,gas temperature and NOx formation at the furnace outlet is conducive to the boiler design,operation and transformation.
What problem does this paper attempt to address?