A Novel Fast Grid-Synchronization Method Under Grid Failure Based on Dual-Input SOGI-FLL

Deng Zhe,Zhou Fengwu,Lin Huipin,Hou Yaojie,Lü Zhengyu
DOI: https://doi.org/10.3969/j.issn.1000-6753.2013.12.005
2013-01-01
Abstract:In order to improve the grid synchronous speed under abnormal conditions, such as voltage imbalance, distortion, and frequency flicker, a novel grid synchronization method is proposed. Compared with traditional SOGI-FLL grid synchronization, an additional input port is added to the SOGI-FLL to establish a dual input SOGI-FLL quadrature signal generator(DISOGI-FLL QSG), so that the convergence rate of SOGI and FLL is greatly improved. With combination of the voltage differential decoupling method and multi-module expansion, the positive or negative fundamental and harmonic voltage information of grid is achieved much faster. Simulation and experiments finally confirm that, compared with SOGI-FLL, the proposed fast decoupling synchronization method performs a doubled convergence rate.
What problem does this paper attempt to address?