Natural ventilation for reducing airborne infection in hospitals

Hua Qian,Yuguo Li,W.H. Seto,Patricia Ching,W.H. Ching,H.Q. Sun
DOI: https://doi.org/10.1016/j.buildenv.2009.07.011
IF: 7.093
2010-01-01
Building and Environment
Abstract:High ventilation rate is shown to be effective for reducing cross-infection risk of airborne diseases in hospitals and isolation rooms. Natural ventilation can deliver much higher ventilation rate than mechanical ventilation in an energy-efficient manner. This paper reports a field measurement of naturally ventilated hospital wards in Hong Kong and presents a possibility of using natural ventilation for infection control in hospital wards. Our measurements showed that natural ventilation could achieve high ventilation rates especially when both the windows and the doors were open in a ward. The highest ventilation rate recorded in our study was 69.0 ACH. The airflow pattern and the airflow direction were found to be unstable in some measurements with large openings. Mechanical fans were installed in a ward window to create a negative pressure difference. Measurements showed that the negative pressure difference was negligible with large openings but the overall airflow was controlled in the expected direction. When all the openings were closed and the exhaust fans were turned on, a reasonable negative pressure was created although the air temperature was uncontrolled.