Mechanism Analysis and Preventive Measures Investigation of Generator Reactive Power Limit Induced Bifurcation

CHEN Lei,MIN Yong
DOI: https://doi.org/10.3321/j.issn:0258-8013.2008.10.003
2008-01-01
Abstract:Limit induced bifurcation(LIB) by generator excitation voltage limit was studied,the critical limit was presented and a mechanism of LIB was proposed. LIB only occurs when the limit is greater than a critical limit. Its sensitivities with respect to parameters were computed,from which a method of preventive control to LIB was derived. LIB can be eliminated by adjusting parameters according to the sensitivities. A new mechanism of LIB was proposed. LIB actually reflects the importance of the dynamic reactive source in maintaining voltage stability. The results of critical limit and sensitivities were analyzed with the mechanism. The influence of static reactive sources on LIB was studied. Static capacitor compensation increases the dependence of voltage stability on dynamic reactive source and can result in the occurrence of LIB.
What problem does this paper attempt to address?