Configuration Design and Experimental Investigation of Fin Used in 5mm Fin-and-tube Heat Exchangers for Air Conditioner

Gao Jingdan,Ding Guoliang,Wu Wei,Gao Yifeng,Song Ji
2013-01-01
Abstract:Optimal louver fins suitable for 5mm diameter tubes are designed by Computational Fluid Dynamic-based method in this study.Based on the design result,a set of fin-and-tube heat exchangers with 5mm diameter tubes are tested to develop correlations to predict the performance of 5mm fin-and-tube heat exchanger. The experimental results indicated that heat transfer rate decreases with the increase of fin pitch,which is more obvious than that of fin-and-tube heat exchanger with 7mm or larger diameter tubes.The water bridge was observed at the bottom of fin in experiments;however,it did not occur on the fin with 7mm or large diameter tubes.A correlation of j factor was developed to predict the heat transfer performance of fin-and-tube heat exchanger with 5mm diameter tubes.The deviations of the proposed j correlation are within ±20%.