Research on Flow Rate Control Method of Variable Water Flow Air-conditioning System

QIN Yun-fei,DING Guo-liang,CHEN Xu
DOI: https://doi.org/10.3969/j.issn.2095-4468.2013.03.108
2013-01-01
Abstract:Presently it is quite common to apply variable water flow rate control in air conditioning system.In order to measure the water flow rate,the conventional method is to install flow meter or flow sensor in the system.However,this method will cause the increase of early stage investment cost for the air conditioning system.In present study,a low cost and practical flow measurement control method was introduced,which calculates water flow by the mathematic model obtained through regression analysis method based on the relationships among water flow,water pump frequency and water head.The experimental verification results show that,the average error of this method is small,and the new method has a good universality; therefore,the new method is very suitable to control the frequency of water pump and the open degree of water bypass valve,and to realize variable water flow rate control.