Analysis of the Increasing Equation of Fire Smoke Plumes in Temperature Stratified Ambient

Jun FANG,Xue-ming SHU,Hong-yong YUAN,Yong-ming ZHANG,Zhao-wu SHEN
DOI: https://doi.org/10.3969/j.issn.1009-6094.2006.04.023
2006-01-01
Applied Mechanics and Materials
Abstract:The present paper has done an investigation and analysis of the movements of smoldering cotton wick smoke and flaming diesel oil smoke plumes in a temperature stratified ambient in a small scale environment through experimental measurements and CFD simulations.The results indicate that in a stratified environment,the temperature difference between the plume and the ambient may eventually vanish and reverse the sign,thus forming a horizontal layer with the plume ceasing to smolder on.Actually,the Morton equation might have been proved to underestimate the actual maximum height of a fire smoke plume.In fact,the diesel oil smoke can be getting decreased faster and rising at a smaller maximum height with the same outlet and stratification conditions.The situation may come to pass at the Morton integral model assumption that the plume is itself similar and the fire smoke is air.By introducing the smoke density factor and self-similarity factor,the Morton equation has thus been discussed and improved.
What problem does this paper attempt to address?