Analysis of Waste Liquid Quality from Sludge Treatment Area in Sewage Treatment Plant

HAO Rui-xia,ZHAO Ji-cheng,MA Ning,WAN Hong-wen,ZHANG Yi
DOI: https://doi.org/10.3321/j.issn:1000-4602.2008.23.019
2008-01-01
Abstract:The characteristics of the waste liquid quality from sludge treatment area in three sewage treatment plants were studied with conventional water quality,three-dimensional fluorescence spectroscopy,ultrafiltration and chromatography analysis methods.The results show that there are higher pollutant loads in the waste liquid,and its quality has a relation to the wastewater and sludge treatment processes and their operation.The waste liquid contains large amount of organic pollutants,the most of which have protein-like,fulvic-like and humic-like with respect to the stability degree of the sludge.There are mainly protein-like organic pollutants in the supernatant from thickening tank and in the filtrate from dehydrator of undigested sludge,and there are mainly fulvic-like and humic-like in the filtrate from dehydrator of digested sludge.The proportion of organic pollutants with apparent molecular weight of more than 6 ku in the mixed waste liquid is more than 70%.Nonylphenol and nonylphenol polyethoxylates,as endocrine disruptors and precursors,are 1.35 to 23.01 μg/L in the waste liquid.
What problem does this paper attempt to address?