Laying Spacing of Detectors of Fiber Bragg Grating Temperature Sensitive Fire Alarm System on External Floating Roof Crude Oil

石凯,姚斌,江梦梦,舒雅
DOI: https://doi.org/10.3969/j.issn.1004-5309.2012.02.008
2012-01-01
Fire Safety Science
Abstract:Fiber Bragg grating temperature sensitive fire alarm system is applied in petrochemical storage area and other inflam- mable and explosive fields, however there is still no relevant national design standard. There are also significant differences in local design specifications of provinces of Anhui and Hubei as for the requirements on laying spacing. Taking external floating roof crude oil storage tank as an example, this paper studies the relationship between laying spacing and diameter of storage tank, by difference temperature or constant temperature detection methods, at two different installation heights. The results show that there is a positive correlation between laying spacing and diameter of storage tank. The fire power is indicated to have a linear relationship with the diameter of storage tank in the beginning stages when the fire power is small. In this stage the lay- ing density should be strengthen to guarantee timely detection when the laying spacing is determined in terms of local stand- ards. As compared to the constant temperature detection method, the. difference temperature method has the advantage in rapid detection of fires, and a relative longer laying spacing can be used.
What problem does this paper attempt to address?