Performance investigation on double-lift LiBr absorption refrigerator in variable conditions

Yao Yuan,Wang Xianlong,Tian Yongjun
DOI: https://doi.org/10.3969/j.issn.1000-6516.2013.03.006
IF: 2.134
2013-01-01
Cryogenics
Abstract:The dependent development of 350 kW DL(Double-Lift) LiBr absorption refrigerator was introduced and experiments were done on the refrigerator in four kinds of variable conditions,which were respectively change in temperature of chilled water(outlet),change in temperature of cooling water(inlet),change in temperature of heat water(inlet) and change in flow rate of heat water.The experimental results show that,in the design value variation range of about 20%,with the increase of the chilled water outlet temperature and inlet temperature of hot water,and the increase of hot water flow,and lowering inlet temperature of cooling water,refrigerating capacity and coefficient of performance(COP) is improved.