Simulation on Fuzzy Control of Steam Temperature for a Lignite-Fired Boiler
Bing-Qi WANG,Xiao-Qu HAN,Cheng ZHANG,Yan ZHOU,Jun-Jie YAN
2017-01-01
Journal of Engineering Thermophysics
Abstract:In this paper,a Fuzzy-PID model was established for a 600 MW supercritical lignite-fired boiler through GSE software,of which the control effect was tested and compared with conventional PID control.The research result showed that when hot flue gas extracting percent stepped from 100% to 50%,the minimum of live steam temperature of Fuzzy-PID strategy was higher by 0.21℃ than conventional PID strategy,while the maximum of which was lower by 0.15℃,and the time of dynamic response reduced by 477 s;Under the same condition,the minimum of reheat outlet steam temperature of Fuzzy-PID strategy was higher by 0.32℃ than conventional PID strategy,while the maximum of which was lower by 0.49℃,and the time of dynamic response reduced by 387 s.It turned out that rapidity and stability of steam temperature adjustnent under Fuzzy-PID control was better than conventional PID control,proving that this Fuzzy-PID strategy could improve the quality of common-used control system.The consequence had certain significance on power plant steam temperature control system optimization.