Comprehensive Evaluation of Sewage Source Heat Pump System Applied in Beijing

张明杨,姜益强,孙丽颖,陈旷,姚杨
DOI: https://doi.org/10.3969/j.issn.1005-0329.2010.05.018
2010-01-01
Abstract:Take an office building in Beijing as an example,the energy consumption index,economic index and environmental index of its sewage-source heat pump system,city heat-supply piping & water chillers system and city heat-supply piping & sewage-source heat pump system were calculated,and a comprehensive evaluation of these three cold,heat source programs by Entropy weight analysis hierarchy process was given.The research results show that the overall performance of sewage-source heat pump system is better than the other two cold,heat programs.On this basis,further calculated the application scope of sewage source heat pump system,when the distance from the sewage plant and the building does not exceed this range,the energy-saving environmental benefits of sewage source heat pump system are much more obvious.