Impact of SVC Control Mode on Voltage Abnormal Oscillation in Wind Power Influx Area
YU Miao,XIE Huan,SONG Wei,WANG Heng,HE Jingbo,XIN Huanhai
DOI: https://doi.org/10.7500/AEPS20160525003
2017-01-01
Abstract:With the increasing penetration of wind power, abnormal voltage oscillation occurs frequently due to utilization of static var compensator (SVC) in large-scale wind power influx area, which attracts attention of researchers working on network planning and operation.An equivalent model of the system is established on the basis of reactive power and voltage control in typical large-scale wind power influx areas with software DIgSILENT/PowerFactory.Two main control modes of SVC, namely constant voltage control and constant reactive power control, are compared and analyzed via adopting different stability analysis methods including eigenvalue analysis in small signal stability, time-domain simulation and Bode plots.Moreover, the derivation method for open loop transfer function in control theory is introduced targeting certain variables.From the perspective of the new controller, the reason why oscillation occurred when it comes into use in actual wind farms is explained in theory.The results demonstrate that SVC with different control modes has different adaptability to the system's change.In terms of the number of wind farm with SVC and the impedance of the system, the constant reactive power control mode performs better than the constant voltage control mode for weak sending end systems in large-scale wind influx area.