Frequency Parameter Identification and Impact Analysis of Load Based on Measured Data
Xiaoming ZANG,Qian CHEN,Xin SHAN,Fangzhao YU,Zhuolin XU,Ping JU
DOI: https://doi.org/10.19635/j.cnki.csu-epsa.000098
2019-01-01
Abstract:In a receiving power grid with ultra-high voltage direct current,the block fault in an inverter station may cause large frequency fluctuations,in which the frequency characteristics of load play an important role in the frequen?cy response of the system. First,the frequency characteristics of new types of load equipment with power electronic in?terface are analyzed,and the trend of frequency characteristics of the total load is studied under the assumption that the proportion of this type of load equipment increases continuously. Then,based on the measured data from East-China power grid under DC block fault,the frequency models of load on the bus and the whole grid are fitted,respectively, and it is concluded that the frequency response characteristics of the total load are becoming weaker. Finally,the mea?surement model and the original model are compared and simulated with East-China power grid as a numerical exam?ple,which verifies that the original load frequency model is prone to be optimistic.