A pass temperature balance control for fired heater based on steady state energy balance

Zhang Weiyong,Lv Wenxiang,Huang Dexian
DOI: https://doi.org/10.3969/j.issn.1001-4160.2008.07.003
2008-01-01
Abstract:A pass balance control scheme to maintain the pass outlet temperature to be same for multi-pass fired heater is proposed and the convergence of the control scheme is analyzed.To avoid the dynamic coupling of different pass streams caused by frequently adjust- ment of pass flow,individual pass flowrate is calculated based on steady state energy balance to drive its outlet temperature arrive at a temperature target,and the control interval is chosen long enough to let the control effects of pass flow change reach steady state.A zone control method is adopted when all the outlet temperature approach to the neighborhood of temperature target.The convergence a- nalysis shows that the proposed strategy is easy to be stabilized and it is behaved near ideal steady state control.To not disturb the pass temperature balance when the setpoint of total load is changed,a load distributed control is designed.Simulation and field implementa- tion results show that the proposed control scheme is very effective and easy to implement.
What problem does this paper attempt to address?