Manganese Removal from the Qiantang River Source Water by Pre-Oxidation: A Case Study

Jian-wen Zhu,Zhen Zhang,Xiao-min Li,Xin-hua Xu,Da-hui Wang
DOI: https://doi.org/10.1631/jzus.a0820409
2009-01-01
Journal of Zhejiang University SCIENCE A
Abstract:We evaluated several different pre-oxidation treatments, namely the introduction of either potassium permanganate (KMnO4), chlorine (Cl-2), or both to remove manganese (Mn) from the Qiantang River source water. Our results showed that Mn removal percentages were 12.7%, 71.0%, 17.4% and 58.7% when none of the oxidants, KMnO4 only, Cl-2 only, or both oxidants were added, respectively. Furthermore, a field study showed that when the available Mn concentration in the source water was 0.14 mg/L, it could be reduced to less than 0.05 mg/L when a solution of KMnO4 (0.47 mg/L) was added as the oxidant.