Research on Room Heating Load with Low-temperature Floor Heating System

Yu ZHAO,Jia-ning ZHAO
DOI: https://doi.org/10.3969/j.issn.1002-8528.2011.10.017
2011-01-01
Building Science
Abstract:Low-temperature floor heating system has been widely used in residential buildings because of its advantage of applying low grade energy.In this paper,using the basic theory of heat transfer,heat transfer models of a room with low-temperature floor heating system and radiator heating system were established respectively.For these two kinds of heating modes,the temperature and the heating transfer coefficient of the interior envelope surface were obtained under the steady-state heat transfer condition and specified indoor air temperature.Also,the heating load difference was analyzed.The results indicated that during the 65% energy-saving stage,the heating load in a room with low-temperature floor heating system was larger than that with the radiator heating system under the same indoor air temperature condition.Furthermore,with respect to these two kinds of heating modes,the difference of the area heating load index was 0.5~0.7 W/m2 in Beijing and was 0.3~0.5 W/m2 in Harbin under different indoor air temperature conditions.