Building Combined Cooling Heat and Power Production System Plan Based on Load Curve and Operation Mode Analysis

林欢欢,黄锦涛,王耀文,梁铁波,常经纬
DOI: https://doi.org/10.13888/j.cnki.jsie(ns).2010.03.010
2010-01-01
Abstract:Each hour thermal,power,cool load of hotel user in cold area are simulated by DOE-2 software,the cogeneration system's operation mode in all conditions analyzed by four-phase bitmap.The optimization of hotel thermal,power,cool cogeneration system plan and operation mode in cold area,taking the net present value as the evaluation index,under the operation mode thermal deciding power,the plan micro gas turbine+hot water type waste heat boiler+single-effect absorption-refrigerator is the optima,the net present value 0.85.
What problem does this paper attempt to address?