Application of EEMD in Power Quality Disturbance Detection of Distribution Network

CHEN Li-ping,ZHANG Jian-wen,ZHANG Lun-jian,WANG Jin-peng
DOI: https://doi.org/10.3969/j.issn.1001-1390.2013.01.007
2013-01-01
Abstract:In the view of the signal of distribution network power quality that is non-stationary signal,this article applied the HHT(Hilbert-Huang Transform) which is based on EEMD(Ensemble Empirical Mode Decomposition) to the power quality disturbance detection.The signal of network of power quality distribution is decomposed into IMF(Intrinsic Mode Function) adaptively by the method.Then the accurate instantaneous frequency and amplitude are obtained after the IMF is operated by HHT,the results can describe the occurrence time of distribution,frequency and amplitude feature.At the same time,the method can overcome the mode mixing caused by EMD(Empirical Mode Decomposition).The method provides a new analytical tool for the distribution of network power quality.The simulation of some distribution network signals results demonstrate the effectiveness of the method.
What problem does this paper attempt to address?