Abstract:Taking the N12180 condenser as an example,the effects of air content and water side fouling on steam side heat transfer coefficient,heat conduction coefficient of cooling tube and average heat transfer coefficient of condenser were numerical calculated by software.The influence mechanism of air content and water side fouling on heat transfer process was analyzed.The results showed that the average heat transfer coefficient of condenser decreased 30%when the condenser inlet air content increasing from 0 to 0.01%.The water side fouling thickness of 0.5mm would result the decreasing of 98%conduction coefficient of cooling tube, and 85%average heat transfer coefficient of condenser.