Study on Control Method of Three-phase APF
Lin ZHOU,Hua ZHUANG,Feng ZHANG,Qiu-hua LI
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.03.036
2007-01-01
Abstract:With the wide application of nonlinear equipment,a great amount of harmonic and reactive currents are generated in power system.Active power filter(APF) is one kind of power electronic devices used to restrain harmonics and compensate reactive power dynamically.It has advantages such as fast response,high control ability and adaptability.So the research on APF is more and more in many countries.One-cycle control(OCC) is a nonlinear control method,its principle is to control the duty-ratio of switch to make the average value of switch variable of the switching converter equal to or proportional to the control reference in each cycle,so that steady-state and dynamic-state errors can be eliminated effectively.Nowadays,OCC has been applied successfully,which displays fast response,excellent power source perturbation rejection and simple control circuit,but it only can compensate harmonics and reactive currents simultaneously.In fact,APF is more used to eliminate harmonics,but compensating harmonics and reactive power simultaneously is in the next place.In order to solve the disadvantages of one-cycle controlled APF,this paper uses an ip-iq method as harmonic currents detecting circuit and one-cycle control as currents tracing control circuit,accordingly,the control function and mathematics model are built.The simulation results verify that this scheme compensates effectively and can provide harmonic current compensation or both harmonic and reactive currents compensation according to requirements of the distorted source voltages flexibly.