DESIGN AND ANALYSIS OF THE ANNUAL RUNNING OF GROUND SOURCE HEAT PUMP SYSTEM

Xie Xiaona,Liu Xiaohua,Jiang Yi
DOI: https://doi.org/10.3321/j.issn:0254-0096.2008.10.007
2008-01-01
Abstract:Ground source heat pump system has been developed quickly in recent years for its low operating costs and no contaminant.The design of geothermal heat exchangers and the annual heat balance problem is the most important and difficult problem in ground source heat pump system.Bessel function was used to establish heat transfer model of U shape buried pipe of geothermal heat exchangers under harmonic and steady boundary conditions.The annual fluid temperature in U shape pipe can be computed using the heat transfer model when annual heating or cooling load is known.The curves are computed showing how maximum and minimum fluid temperature varies with the unit length design load of U shape pipe.The curves can be used to design U shape pipe.The annual total heating and cooling energy,the peak heating and cooling load should meets some conditions to assure the ground source heat pump system nm well.The conditions were studied and could be used to design the heating and cooling source in a building.
What problem does this paper attempt to address?