Analysis of static voltage stability of grid-connected wind farm system based on ESA

ZHANG Jian-ping,DING Quan-fei
DOI: https://doi.org/10.3969/j.issn.1674-3415.2010.21.007
2010-01-01
Abstract:On the basis of eigenvalue structure analysis method(E SA),t he impact of integration of wind farm equipped with induction generator on the static voltage stability of power systems is studied.T aking the minimum module eigenvalues and the participation factors as indicators,t he static stability margin is clearly provided,as well as the most unstable node and region of the whole power system.A standard IEEE test system with 10 machines and 39 nodes including wind farm is applied for calculation and analysis.T he results show that the wind farm and its associated nodes have strong participation features,and they are the critical region which affects the system voltage stability ;t hat the integration of wind farm reduces the static stability margin and extends the weak stability region,and the installation of compensators in the terminal of wind turbine generator system can effectively improve the system's static stability margin;and that the integration of wind farm reduces the system's load margin,but it has no significant effects on the instability region and instability mode while the system reaches to its limit load.
What problem does this paper attempt to address?