Experimental study of an air conditioning system directly using soil as heat sink in cold areas

Zheng Maoyu,Li Zhongjian,Wang Fang,Han Zongwei
DOI: https://doi.org/10.3969/j.issn.1002-8501.2007.10.026
2007-01-01
Abstract:Presents a novel conception of directly using soil as heat sink to cool buildings and establishes an experimental system in Harbin area. The experimental results during a cooling season indicate that the seasonal cooling performance factor of the system is 9.85, the average cooling rate is 0.93 kW and the effective thermal radius of the cold extraction well is less than 3 m, and that the soil direct cooling system presented has great potential in energy efficiency within a definite region.
What problem does this paper attempt to address?