Abstract:A closed-loop experimental setup was built for the study of the confined jet array impingement boiling of 43% mass concentration aqueous ethylene glycol solution.The rectangular heating surface is 20 mm by 40 mm and the in-line jet array has the jet orifice diameter d=1mm,the dimensionless jet-to-target spacing H/d=1,1.5 and 3,and the dimensionless jet-to-jet spacing S/d=4 and 5.The experiments were performed at different system pressure,jet impingement velocity and inlet sub-cooling.The experimental results show that in single-phase convective cooling regime,the smaller the jet-to-jet spacing,the larger the heat transfer coefficient,and there is an optimal jet-to-target spacing that makes the heat transfer best.In nucleate boiling regime,the jet-to-target distance has negligible effects in the range of experimentally tested parameters,but has an important influence on the critical heat flux(CHF).The higher the system pressure and the smaller the jet-to-jet spacing,the larger the heat transfer coefficient.