Effects of non-uniform fire protection coating on temperature distribution and deformation of a simply supported steel beam under fire conditions

Yu-qin ZHOU,Bin YAO,Jun HU,Bing GAO
DOI: https://doi.org/10.3969/j.issn.1004-5309.2008.04.007
2008-01-01
Fire Safety Science
Abstract:Fire protection coating on the steel member's surface was generally assumed to be with a uniform thickness distribution.However,the coating may be non-uniform due to many factors,which might affect the fire safety of the steel member.In this paper,the FEM software ANSYS was used to analyze the differences in both surface temperature and deformation of a simply supported steel beam covered with various kinds of non-uniform fire coating under the validated consumption that fire coating thickness can be described as normal distribution normal distribution.The results indicate that the temperature is no longer uniform along the longitudinal direction of the steel beam,but shows regional distribution when the fire coating is non-uniform,and the temperature distribution of the cross section is no longer symmetry.At the same time,the non-uniform thickness of fire coating has little effect on the axial deformation but an obvious effect on the deflection of the steel beam.The standard deviation will affect the temperature distribution and deformation significantly,and a higher standard deviation will lead to a bigger relative error of temperature distribution and deformation.
What problem does this paper attempt to address?