Identification of synchronous generator practical parameters based on time interval
Juan ZHAO,Yi-ping YU,Yao WANG,Jian-hua SUN,Hong-jun FU,Zheng-li ZHANG,Ping JU
DOI: https://doi.org/10.3969/j.issn.1673-9140.2014.01.008
2014-01-01
Abstract:The leading practical parameters of synchronous generators are different at different time stages in the dynamic process.At first,the traj ectory sensitivity features of synchronous generator practical parameters were analyzed by the excitation disturbance analysis method and it indicated that different parameters of synchronous generators had different traj ectory sensitivity features according to time intervals.And a time interval based identification strategy of synchro-nous generator parameters was proposed in this paper.With steady-state data before and after the disturbance,the steady-state parameters of synchronous generator can be identified.Then,with the subtransient-state data and transient-state data,the subtransient parameters and transient pa-rameters can be identified respectively.Finally,by a single machine infinite bus system,the ef-fectiveness of above method was verified.