Transient Analysis of DFIG with a Crowbar Circuit During the Voltage Dip

CHENG Meng-zeng,DOU Zhen-lan,ZHANG Jian-wen,CAI Xu
DOI: https://doi.org/10.3969/j.issn.1674-3814.2012.05.011
2012-01-01
Abstract:In order to study voltage sag adaptability of doubly-fed induction generators(DFIG) in power system and achieve low voltage ride-through capability,this paper analyzes the electromagnetic transients within DFIG through approximated analytical expression of stator fault current and rotor fault current obtained by the superposition between transient current based on vector method and steady state current based on equivalent circuit method under the following circumstances: stator terminal three-phase symmetrical voltage dip,the rotor side converter cut off,and the crowbar circuit in operation.On the base of the theory analysis,a 2 MW DFIG model is established by PSCAD and its experiment on the prototype validates the effectiveness of approximated analytical expression of fault current based on the superposition method between transient current and steady state current on a 7.5 kW DFIG platform,which could present the transient changes of the DFIG flux and current correctly.
What problem does this paper attempt to address?