Application study on radiator heating system with air-source heat pump in Shanghai area

Zhou Bin,Tan Hongwei,Wang Liang,Chen Shuqin,Zhuang Zhi
2013-01-01
Abstract:Taking the air-source heat pump(ASHP)heating system with radiators of a public building in Shanghai as the research object,tests the indoor air temperature,the temperature of envelope surface,supply and return water temperature of the space heating system,and heat pump energy consumption.Calculates the heating coefficient of performance of the system and the ASHP unit,and analyses thermal comfort of the heating system with thermal comfort evaluation of indoor personnel.The results show that under the experimental conditions,the COP of the heating system is about 1.81,and the average indoor temperature is 21 ℃;compared with the conventional heating system,the COP of the ASHP heating system with radiators is lower,but the indoor temperature is more stable,and the vertical temperature difference is smaller;as the rate of temperature rise is slow,the operation mode of continuous heating should be taken if the heating system with radiators is used in the offices with large space.