Analysis of Iced Transmission Line Galloping and Effect of Anti-Galloping

孙珍茂,楼文娟
DOI: https://doi.org/10.3969/j.issn.1000-3835.2010.05.031
2010-01-01
Abstract:The non-linear differential equations of iced transmission line galloping were derived with Lagrange equation for the fixed-fixed transmission lines installed with masses or detuning pendulums.The method to calculate the critical wind velocity was proposed.The non-linear differential equations were solved by Runge-Kutta method to get the galloping response in time domain.A tested transmission line was calculated and analyzed as an example.The results showed that the torsional galloping can cause lateral galloping when their vibration frequencies are close to each other;the amplitude of galloping is relatively large when the wind velocity is in a certain range;the galloping amplitude changes with the conductor sag significantly and there exists the worst sag to cause the largest galloping amplitude;the method to prevent galloping with masses can reduce but not suppress the amplitude of galloping;but the method to prevent galloping with detuning pendulums can eliminate galloping completely.