Drum water level control method based on fuzzy control and feed-forward compensation

Zhang Xiang,Lu Jidong,Lu Zhimin,Dong Meirong
DOI: https://doi.org/10.13245/j.hust.2012.11.027
2012-01-01
Abstract:The flow rate and temperature were introduced into the control algorithm of drum water level of waste heat boiler.Based on fuzzy control,two fuzzy controllers were designed.In this scheme,the output amendments of water flow from the two controllers and the feed-forward amendment of main steam flow modify the water flow setting value from traditional cascade three impulses PID proportional-integral-derivative controller in the water level regulation loop.It was applied and tested in a waste heat power generation plane.The result demonstrates that the stability of the drum water level can still maintain in the substantial changes of the cement waste heat boiler inlet flue gas temperature and flow conditions.The control result of drum water level in fuzzy feed-forward control is better than in conventional PID control.
What problem does this paper attempt to address?