Experiment on site operational stability of optical current transformer

YU Wenbin,JIANG Bo,ZHANG Guoqing,WANG Guizhong,SHEN Yan,GUO Zhizhong
DOI: https://doi.org/10.3969/j.issn.1006-6047.2012.04.010
2012-01-01
Abstract:The site operational performances of optical current transformer are evaluated in error calibration,energy measurement statistics and metering system overall calibration.The error calibration data before and during site operation show the error change is less than 0.1 %,satisfying the requirement of class 0.2S.Two independent measuring systems are established for the long-term comparison of site operational data to demonstrate the long-term operating stability of digital energy metering system under various environmental conditions.The overall calibration data of digital energy metering system indicate that,at rated power,the uncertainty is 9.0 × 10-5,the confidence probability is 97.15 % and the system comprehensive error is 1.013 %,satisfying the requirements of codes.