Wireless Parallel Control Without Output Current Sensing for Three-phase Inverter

YIN Yi-di,MA Hao,LIN Zhao,LI Ting
DOI: https://doi.org/10.3969/j.issn.1000-100X.2013.04.004
2013-01-01
Abstract:On conventional droop control scheme,the output active and reactive power of inverters need to be calculated by the information collected by the output voltage and current sensor.This paper proposes a simple control strategy of wireless parallel operation for three-phase inverter,which can work without the use of output current.The input power which can be simply calculated by input voltage and input current is the only information used in droop control.Each inverter works in voltage single-loop control,thus,no output current sensor is needed in the whole system which can be helpful to the reliability.In order to show the performance of the system,two parallelled-connected three-phase inverters are built and tested.Experimental results are presented to prove the validity of the proposed control scheme.
What problem does this paper attempt to address?