Simulation and Design of Electric Field Distribution for the Incoming Conductor Between 330 Kv Terminal Tower and 750 Kv Substation
Yunfei Fan,Peng Liu,Wei Shen,Hao Wen,Chuang Liu,Jun Zhang,Zongren Peng
DOI: https://doi.org/10.1007/978-981-99-7405-4_21
2023-01-01
Abstract:During the field research of a 750 kV substation, corona discharge was found on the incoming conductors between the 330 kV terminal tower and the portal frame. To improve the corona discharge situation, the electric field of the incoming conductors was studied. A three-dimensional electric field simulation model of the incoming conductors between the 330 kV terminal tower and the portal frame in the 750 kV substation was established by using COMSOL Multiphysics, then surface electric field distribution of the incoming conductors was calculated. The impact of three factors—the width of the terminal tower cross-arm, the distance between the terminal tower and the portal frame, and the diameter of the incoming conductor—on the maximum electric field strength of the conductors was analyzed. The results showed that increasing the terminal tower cross-arm, increasing the distance between the terminal tower and the portal frame, and increasing the diameter of conductors can all reduce the surface electric field strength. The influence of increasing the diameter on electric field strength is significant. As the diameter increases from 26.6 to 33.6 mm and 36.2 mm, the maximum field strength decreases by 22.1% and 26.7%, respectively. The calculation results can provide the design basis for the incoming conductor layout and selection of 750 kV substations.