Experimental Study on Liquid Distributor of Absorption Heat Pump with Falling Film Outside Vertical Tube

Sun Jian,Hu Peng,Fu Lin
DOI: https://doi.org/10.3969/j.issn.0253-4339.2010.02.017
2010-01-01
Abstract:The absorption heat pump technology has been an important building energy-saving technology due to its effective utilization of low-grade heat energy and electrical energy saving.The absorber performance is mainly determined by heat transfer and mass transfer coefficients of tubes which are directly influenced by falling film distribution on the surface of heat transfer tubes.The liquid distributor is a critical part for realizing falling film.In this research,four liquid distributor samples with different types were manufactured and the experiment on liquid falling film outside vertical tubes was conducted using Φ19 and Φ25 copper tubes.The relationship between liquid the static height and the liquid flux of each distributor was analyzed and achieved.The correlation of the flux coefficient and the Renault number for each liquid distributor was obtained.In addition,the method to improve liquid distribution performance was presented on the basis of the experimental results.An optimized liquid distributor has been successfully applied in the first prototype of vertical falling film absorption heat pumps in China.