Comparison on Condensation Heat Transfer Performance of R407C Outside Petal-Shaped Finned Tube With Low Finned Tube

QIN Peng,LING Zi-Ye,XU Tao,Zhengguo Zhang.,YE Zhuo-Cheng
2013-01-01
Journal of Engineering Thermophysics
Abstract:Condensation heat transfer coefficients(HTCs) of zeotropic refrigerant mixture R407C on single horizontal petal shaped finned(PF) tube and low finned tube were experimentally measured. All measurements were taken at the vapor temperature 39℃?with the wall subcooling of 3~9℃? The results showed that the enhancement factor provided by the petal-shaped finned tube was 4.6~5.4, the outside condensation HTCs of petal-shaped finned tube was about 1.15~1.25 times as large as that of low finned tube at the same wall subcooling.It is a promising route to use petal-shaped finned tube instead of low finned tube for improving the performance of condensation heat transfer of nonazeotropic mixture.
What problem does this paper attempt to address?