Typical Characteristics of Gas Turbine-Based CCHP System with Inlet Air Cooling

Fei Zeng,Cheng Yang,Zeliang Yang
DOI: https://doi.org/10.1109/APPEEC.2011.5748589
2011-01-01
Abstract:Gas turbine-based CCHP system performance is strongly influenced by the ambient conditions. Gas turbine inlet air cooling technology improves gas turbine performance and its integrated CCHP system performance as well. Using the typical analytical characteristics of the system components, i.e. , small-sized gas turbine, single pressure HRSG and double-effect water/LiBr absorption chiller, this paper investigated the effect of gas turbine inlet air cooling on the operation performance of an integrated CCHP system. Thermal efficiency, equivalent exergy efficiency and economic exergy efficiency of the system were also discussed. The results indicate that, every 1°C increase in gas turbine inlet air temperature averagely results in 0.879% decrease in power capacity, 0.282% decrease in heat capacity and 0.205% decrease in cooling capacity. Gas turbine inlet air cooing influences the CCHP thermal efficiency and economic exergy efficiency slightly, even brings out a negative increase.