Time Synchronization Attack in Smart Grid-Part II: Cross Layer Detection Mechanism

Zhenghao Zhang,Matthew Trinkle,Aleksandar D. Dimitrovski,Husheng Li
DOI: https://doi.org/10.48550/arXiv.1204.0462
2012-04-02
Cryptography and Security
Abstract:A novel time synchronization attack (TSA) on wide area monitoring systems in smart grid has been identified in the first part of this paper. A cross layer detection mechanism is proposed to combat TSA in part II of this paper. In the physical layer, we propose a GPS carrier signal noise ratio (C/No) based spoofing detection technique. In addition, a patch-monopole hybrid antenna is applied to receive GPS signal. By computing the standard deviation of the C/No difference from two GPS receivers, a priori probability of spoofing detection is fed to the upper layer, where power system state is estimated and controlled. A trustworthiness based evaluation method is applied to identify the PMU being under TSA. Both the physical layer and upper layer algorithms are integrated to detect the TSA, thus forming a cross layer mechanism. Experiment is carried out to verify the effectiveness of the proposed TSA detection algorithm.
What problem does this paper attempt to address?