Cascading Synchronization Instability in Multi-VSC Grid-Connected System

Xikun Fu,Meng Huang,Shangzhi Pan,Xiaoming Zha
DOI: https://doi.org/10.1109/tpel.2022.3153283
IF: 5.967
2022-07-01
IEEE Transactions on Power Electronics
Abstract:In this letter, a cascading synchronization instability phenomenon is reported in a multi-voltage-source-converter (VSC) grid. By adopting the equal area criterion, it is revealed that during the fault transient, there is static interaction that increases equivalent mechanical power for the original stable-operating VSC. Due to the fast power angle swing of the unstable VSC, there is nonnegligible dynamic interaction, which may decrease its synchronization stability margin. The effect of system parameters on synchronization stability is studied, and the simulation and experimental results verify the analysis.
engineering, electrical & electronic
What problem does this paper attempt to address?