Performance of Plain and Galvanized Reinforcing Steel During the Initiation Stage of Corrosion in Concrete with Pozzolanic Additions

E. I. Moreno,A. Saguees,R. Powers
Abstract:The pH of the concrete pore solution is expected to be somewhat lower in concretes using pozzolanic additions than in concrete using unblended cements. Variations in pH pore solution may hold the key to explaining conflicting reports on the performance of galvanized rebar. To examine that factor, plain and galvanized rebars have been tested for over two years in concrete specimens made with cement type 2, with various contents of fly ash and silica fume. Electrochemical impedance measurements and sensitive polarization techniques have been used to measure the rate of metal dissolution in the absence of chloride contamination at two different levels of concrete moisture. The plain steel specimens have shown little tendency for passivation in two of the cement compositions with the highest levels of pozzolanic addition. The galvanized steel passivated in all cases and showed apparent corrosion current densities of less than 0.3 {micro}A near the end of the test. Implications of the length of the corrosion initiation period and on current materials selection criteria are presented.
What problem does this paper attempt to address?